GENERAL INFORMATION |
|
0001 |
0002 |
0004 |
0008 |
0015 |
0022 |
Applied Motor |
Heavy Duty |
HP |
0.125 |
0.25 |
0.5 |
1.0 |
2.0 |
3.0 |
kW |
0.1 |
0.2 |
0.4 |
0.75 |
1.5 |
2.2 |
Rated Output |
Rated Capacity(KVA) |
0.3 |
0.6 |
0.95 |
1.9 |
3.0 |
4.5 |
Rated Current(A) |
0.8 |
1.4 |
2.4 |
4.2 |
7.5 |
10.0 |
Frequency(Hz) |
0~400Hz |
Voltage(V) |
3 phase 200-240V |
Rated Input |
Rated Current(A) |
1.0 |
1.8 |
3.7 |
7.1 |
13.6 |
18.7 |
Frequency(Hz) |
50~60Hz (±5%) |
Voltage(V) |
1 phase 200-240Vac (-15% to +10%) |
Cooling Type |
Natural cooling |
Forced fan cooling |
Certificate/Compliance |
UL, CE |
Weight(Kg) |
0.66 |
1 |
1.45 |
|
Environment |
Ambient Temperature* |
-10~50℃ (14~122℉), Ambient temperature under the condition of no ice or frost |
Ambient Humidity |
Relative humidity less than 95% RH (to avoid condensation forming) |
Storage Temperature |
-20~65℃ (-4~149℉) |
Surrounding Environment |
Prevent contact with corrosive gases, inflammable gases, oil stains, dust, and other pollutants (Pollution degree 2 environment) |
Altitude / Oscillation |
Below 1,000m, below 9.8m/sec2 (1G) |
Pressure |
70~106kPa |
* 0.1~0.2kW products can be operated at a maximum of 50℃. However, the lifespan of the product maybe reduced when operating continuously with a full load when the ambient temperature exceeds 40℃ |
|
|