MCCB Molded Case Circuit Breakers

Key Features

  • FOR POWER DISTRIBUTIONr
    • High breaking capacity
    • Optimum coordination technique
    • Powerful engineering tools
    • Reverse feeding
  • FOR PROTECTION OF MOTORS AND THEIR CONTROL DEVICES
    • Optimal overload protection
    • Side-by-side installation
    • Easy connection with RJ45 port
    • Guaranteed Short Circuit Current Ratings
  • FOR EXTENSIVE APPLICATIONS
    • Wide range of optimized auxiliaries and accessories
  • FOR CONTROLLING AND DISCONNECTING CIRCUITS
① Performance
Rating 80% 100% kA
120/ 240Vac E ET 50
N NT 65
H HT 100
240Vac E ET 50
N NT 65
H HT 100
480Vac E ET 25
N NT 35
H HT 65
600Y/ 347Vac E ET 14
N NT 18
H HT 35
② Trip Unit
FTU: Fixed Thermal, Fixed Magnet
FMU: Adj. Thermal, Fixed Magnet
MCS: Molded Case Switch
③ Amperes
15A 15 Amperes
20A 20 Amperes
25A 25 Amperes
30A 30 Amperes
35A 35 Amperes
40A 40 Amperes
45A 45 Amperes
50A 50 Amperes
60A 60 Amperes
70A 70 Amperes
80A 80 Amperes
90A 90 Amperes
100A 100 Amperes
④ Poles
2P Twe
3P Three
Terminals
LL Lugs Line/Load Side
L Lugs Line Side
LO Lugs Load Side
Blank Bolt-on
⑥Suffix
UL UL
   
① Frame
150 150F
250 250F
400 400AF
600 600AF
② Performance
Rating 80% 100% kA
240Vac N NT 65
H HT 100
L LT 150
480Vac N NT 35
H HT 65
L LT 100
600Vac N NT 18
H HT 35
L LT 50
③ Trip Unit
FTU Fixed Thermal, Fixed Magnet
FMU Adj. Thermal, Fixed Magnet
ATU Adj Thermal & Magnet
ETS Electronic trip unit standard
ETM* Electronic trip unit muli function
MCP: Motor Circuit Protector
MCS Molded Case Switch
* UTS400, UTS600 only
Amperes
UTS150 UTS250 UTS400 UTS600
40 150 250 500
50 160 300 600
60 175 350
70 200 400
80 225
90 250
100
125
150
Poles
2P Twe
3P Three
Terminals
LL Lugs Line/Load Side
L Lugs Line Side
LO Lugs Load Side
Blank Bolt-on
     
① Frame
800 800AF
1200 1200 AF
② Performance for 800 AF
Rating 80% 100% kA
240Vac N NT 65
H HT 100
L LT 150
480Vac N NT 35
H HT 65
L LT 100
600Vac N NT 18
H HT 35
L LT 50
② Performance for 1200AF
Rating 80% 100% kA
240Vac N NT 50
H HT 100
P PT 65
L LT 150
480Vac N NT 35
H HT 65
P PT 50
L LT 100
600Vac N NT 18
H HT 25
P PT 50
L LT 35
③OCR-I
N Normal
A Ammeter
P Power meter
S Super meter
MCP Motor Circuit Protector
MCS Molded Case Switch
* UTS400, UTS600 only
OCR-II
G Communication(X)
E Com.(X) + Outer CT (G/F)
C Communication(O)
X Com.(O) + Outer CT (G/F)
OCR-III
0 Power(X), 60Hz
1 AC/DC 100~250V, 60Hz
2 DC 24~60V, 60Hz
5 Power(X), 50Hz
6 AC/DC 100~250V, 50Hz
7 DC 24~60V, 50Hz
Amperes
UTS800 UPS1200
400 800
600 1000
630 1200
800
⑦Poles
3 Three
Terminals
LL Lugs Line/Load Side
L Lugs Line Side
LO Lugs Load Side
Blank Bolt-on
     
   2023 © Amerimation Inc.Volume 4.0.1