LSLV SP100 Bypass VFD Packaged Solution for Variable Torque Fan and Pump Applications

Key Features

     
  • 3 Contactors Bypass
  • HAND/OFF/AUTO Keypad and on Bypass
  • Built-in DC Reactor
  • Easy Wiring and Installation
  • Standard BACnet, Metasys N2, Modbus RTU Comm. Protocol
  • Auto Bypass Function
  • Motor OL Trip Detection
  • NEMA1 Enclosuree
  • KEB, Kinetic Energy Buffering Function
  • Fire Mode
  • Built-in 5 Relay Outputs
  • Real Time Clock
① Rated Motor
0055 5.5kW
0075 7.5kW
0110 11kW
0150 15kW
0185 18.5kW
0220 22kW
0300 30kW
0370 37kW
0450 45kW
0550 55kW
② Input Voltage
2 208VAC / 230VAC, 3-Phase, 60Hz
4 460VAC, 3-Phase, 60Hz
③ Keypad
E LED Keypad
④ Enclosure
X UL Type 1
EMC Filter
F Built-in EMC Filter (C3 type filter / Only available for 460V, 2~40hp)
N No EMC Filter
⑥ Reactor
D DC Link Reactor (Provided as Standard) / Model for the Quick Ship Program
A 3% Impedance AC Line Reactor
⑦ Configuration
3 3 contactor Basic Bypass
   
Environmental
Enclosure Type 1
Ambient Temperature +14℉ to +104℉ (-10℃ to +40℃)
Storage Temperature -4℉ to +149℉ (-20℃ to +65℃)
Humidity 5% to 95% with no condensation
Altitude 0 to 3,300 ft. (1,000m) without derating, derate output current by 1% for each additional 330 ft (100m)
Codes and Standards
UL, cUL Listed per UL508A
Conforms to applicable NEMA ICS, NFPA, & IEC Standards
Electrical
Input Voltage: Nominal – Phase 208VAC, 230VAC, 460VAC – 3 Phase
Input Voltage: Tolerance, Unbalance +/-10%, ≤3%
Input Frequency 60Hz +/-5%
Displacement Power Factor ≥0.97
Output Frequency 0.00 ~ 400.00Hz
Motor Control Method V/F for all capacity range
PWM Switch Frequency 1 ~ 15kHz (2~ 40HP) 1 ~ 10kHz (50 ~ 75HP)
Drive Overload Capacity 120% for 1 min – 208V/230V: 2~25HP, 460V: 2~75HP
Motor Overload Programmable overload / EMPR
Torque Boost Manual 0~15% boost, automatic torque boost available
Speed Reference Keypad, 0~10V, -10~10V, 0~20mA, RS485, Fieldbus, Pulse – 208V/230V: 2~25HP, 460V: 2~75HP
Speed Reference Resolution Digital command: 0.01Hz Analog command: 0.06Hz (60Hz standard)
Acceleration/Deceleration Time 0.00 ~ 6000.0 seconds
Jump Frequencies 3 programmable jump frequency
Output Signals Qty 4: N.O. dry contacts rated 5A @ 230V max, functionality: Drive Run, Drive Fault, Bypass Run, & Damper Control (for Fan) Qty 1: Open Collector rated 50mA @ 26VDC max, functionality: Drive Run (for Pump) Qty 1: Form C dry contacts rated 2A @ 230V max, functionality: Drive Fault (for Pump) Qty 1: 0 to 10VDC or 4 to 20mA, user selectable programmable analog signal (for both Fan & Pump)
Operation Features
Soft Fill Prevents pump damage caused by dramatic pressure changes during initial operation.
Start/End Ramp Prevents pump damage by changing the acceleration and deceleration ramp profile during initial pump operation and stop.
Decel Valve Ramp Prevents pump or pipe damage caused by sudden pressure changes when pumps are stopped or valves are closed.
Scheduling (Time Event: Real Time Clock) Real Time Clock allows sequencing of selected functions during pre-defined time periods.
Flow Compensatione Compensates for hydraulic losses due to elevation or long pipe lengths.
Pump Clean Removes foreign substances from the pump cavity to extend life and improve efficiency.
Load Tuning Estabilishes load curves (current & power) to define load characteristics for under torque and pump clean funtions.
Fire Mode Operates continuously to protect critical systems during emergency situations under set frequency and direction.
Energy Savings Display Commercial energy consumption is compared to the energy utilized by the VFD to calculate the amount energy savings.
Certificate/Compliance UL, CE
Power-On Resume Automatic restart upon power interruption.
Sleep, Sleep Boost, Wake-up Standby mode during PID operation for energy savings and reduction of pump wear.
Auto Torque Boost Manual or automatic voltage compensation for varying load profiles
Lubrication Control Lubrication output signal for a defined time period prior to drive control starting.
Damper Control Damper control with end-switch confirmation with programmable time period.
Level Detection User defined low and high detection limits based upon voltage, current or feedback.
Pipe Break Detection Upon PID operation, pipe breakage or leakage is detected to display a warning or fault condition.
Underload Detection No flow or pump dry detection with selectable response.
Motor Pre-heat Prevents condensation in the motor by injecting direct current during idle states.
Kinetic Energy Buffering Upon loss or momentary power interruption, the drive maintains DC bus voltage by controlled regeneration of the load.
Macro Setting Application specific parameter groups for commonly used functions.
Bypass Features Manual bypass selection.
Automatic transfer to bypass
Bypass run indication
Motor overload indication.
Power on indication.
Hand/Off/Auto selector switch.
VFD/Off/Bypass selector switch.
Adjustable trip class for bypass contactor.
Damper end switch logic with notification.
Drive and bypass input/output contactors.
Drive input isolation contactor
Control power transformer with fusing.
Five built-in relay outputs.
Built-in DC reactor. / Built-in 3% AC Line reactor as an option.